Echo SmartSpace Controller
SmartSpace Controllers are available in single- or dual-zone 120/277V configurations and provide on/off functionality for all types of lighting fixtures up to 20 amps, offer 0-10V dimming for direct control of compatible LED drivers and fluorescent dimming ballasts, provide 24 Vdc power to an auxiliary device (such as an occupancy sensor), and receive dry contact input to initiate control events across the system. The EchoAccess Mobile App provides configuration of the Echo SmartSpace Controller features. The dots at the bottom of the screen indicate additional pages of configuration. Swipe left or right to access the Echo SmartSpace Controller, Echo SmartSpace Controller, or Echo SmartSpace Controller.
Use the drop down menus and keypad to set the Event Actions and any additional options that display according to the action selected.
Note: Regardless of the Aux Input Mode selected, all event types will display for configuration. You only need to configure the related event for your input mode. For example, when Occupancy Input Mode is selected, set the Occupancy and Vacancy Events, and when Photo Input Mode is selected, set the Bright and Dark Events.
-
Aux Input Mode - use the drop down menu to select the Auxiliary Input Mode to either Disabled, Occupancy, or Photo.
- Contact Status - a read only status of the auxiliary input, based on the type of Aux Input Mode that is configured.
- Disabled - displays Contact Closed / Contact Open
- Occupancy - displays Occupied / Vacant
- Photo - displays Contact Closed, dark / Contact Open, bright
Occupancy Event (Aux Contact Closed)
- Action - use the drop down menu to set the event Action that will take place when occupancy is detected. Additional menu options will display based on the Action selected (e.g., if the Action is set to Preset Active, Preset Number and Timing (in seconds) displays for specification).
Vacancy Event (Aux Contact Open +30 seconds)
Note: A SmartSpace controller builds in a 30 second vacancy timeout upon receiving a vacancy command via the contact closure to avoid false vacancy triggers.
- Action - use the drop down menu to set the event Action that will take place when vacancy is detected. Additional menu options will display based on the Action selected (e.g., if the Action is set to Preset Active, Preset Number and Timing (in seconds) displays for specification).
Bright Event (Aux Contact Open)
- Action - use the drop down menu to set the event Action that will take place when the Contact Status is in Bright state. Additional menu options will display based on the Action selected (e.g., if the Action is set to Preset Active, Preset Number and Timing (in seconds) displays for specification).
Dark Event (Aux Contact Closed)
- Action - use the drop down menu to set the event Action that will take place when the Contact Status is in Dark state. Additional menu options will display based on the Action selected (e.g., if the Action is set to Preset Active, Preset Number and Timing (in seconds) displays for specification).
Swipe to the left or right to access the second page and set the default timing and circuit values for each programmed preset.
- Timing - use the keypad to set the preset fade timing used for all configured circuits in this preset
- Circuit # Value - use the keypad to set the intensity level for each individual circuit in this preset
Configuration Sharing
Five buttons are available at the bottom of the configuration screen.