This reference guide defines the BACnet Protocol Implementation Conformance Statement (PICS) for use with ETC's Unison Paradigm Central Control Server (P-CCS).
Vendor Name: Electronic Theatre Controls, Inc. (ETC) – BACnet Vendor ID # 433
Product Name: Unison Paradigm Central Control Server
Product Model Number: P-CCS
Application Software Version: v5.0 or newer
The P-CCS BACnet Interface allows a BACnet Client to interface with and control a Unison Paradigm lighting system. BACnet IP Clients physically connect via the Secondary Network Interface of the P-CCS, positioning the server as a gateway between the Unison system and BACnet client applications. It exposes a series of BACnet objects that reflect the state / condition of Paradigm lighting devices and permit control.
£ BACnet Operator Workstation (B-OWS)
£ BACnet Advanced Operator Workstation (B-AWS)
£ BACnet Operator Display (B-OD)
£ BACnet Building Controller (B-BC)
£ BACnet Advanced Application Controller (B-AAC)
£ BACnet Application Specific Controller (B-ASC)
£ BACnet Smart Sensor (B-SS)
£ BACnet Smart Actuator (B-SA)
R BACnet Gateway (B-GW)
DS-RP-B
DS-RPM-B
DS-WP-B
DS-WPM-B
Application Service | Initiates Requests | Executes Requests |
---|---|---|
Acknowledge Alarm | – | – |
ConfirmedCOVNotification | – | – |
ConfirmedEventNotification | – | – |
GetAlarmSummary | – | – |
GetEnrollmentSummary | – | – |
SubscribeCOV | – |
✔ |
UnconfirmedCOVNotification |
✔ |
– |
AtomicReadFile | – | – |
AddListElement | – | – |
RemoveListElement | – | – |
CreateObject | – |
✔ |
DeleteObject | – |
✔ |
ReadProperty | – |
✔ |
ReadPropertyConditional | – | – |
ReadPropertyMultiple | – |
✔ |
WriteProperty | – |
✔ |
WritePropertyMultiple | – |
✔ |
DeviceCommunicationControl | – | – |
ConfirmedPrivateTransfer | – | – |
ReinitializeDevice | – | – |
ConfirmedTextMessage | – | – |
UnconfirmedTextMessage | – | – |
UTCTimeSynchronization | – |
✔ |
Who-Has | – | – |
I-Have | – | – |
Who-Is | – | – |
I-Am | – |
✔ |
VT-Open | – | – |
VT-Close | – | – |
VT-Data | – | – |
Authenticate | – | – |
Request Key | – | – |
Object-Type | Supported | Dynamically Creatable | Dynamically Deletable | Optional Properties Supported | Writable Properties |
---|---|---|---|---|---|
|
|
|
|
|
|
Analog Input |
✔ |
– |
– |
Description |
|
Analog Output |
✔ |
– |
– |
Description |
Present_Value |
Analog Value |
– |
– |
– |
|
|
Binary Input |
✔ |
– |
– |
Description |
|
Binary Output |
✔ |
– |
– |
Description |
Present_Value |
Binary Value |
– |
– |
– |
|
|
Calendar |
– |
– |
– |
See Timed Event below |
See Timed Event below |
Command |
– |
– |
– |
|
|
Device |
✔ |
N/A |
N/A |
|
Location, |
Event Enrollment |
– |
– |
– |
|
|
File |
– |
– |
– |
|
|
Group |
– |
– |
– |
|
|
Loop |
– |
– |
– |
|
|
Multi-state Input |
– |
– |
– |
|
|
Multi-state Output |
– |
– |
– |
|
|
Notification Class |
– |
– |
– |
|
|
Program |
– |
– |
– |
|
|
Schedule |
– |
– |
– |
(see Timed Event below) |
(See Timed Event below) |
Macro (ETC) |
✔ |
– |
– |
ETC specific properties |
Yes, Present_Value |
Preset (ETC) |
✔ |
– |
– |
ETC specific properties |
Yes, Present_Value |
Override (ETC) |
✔ |
– |
– |
ETC specific properties |
Yes, Present_Value |
Group (ETC) |
✔ |
– |
– |
ETC specific properties |
Yes, Present_Value |
Space (ETC) |
✔ |
– |
– |
ETC specific properties |
Yes, Present_Value |
Channel (ETC) |
✔ |
– |
– |
ETC specific properties |
Yes, Present_Value |
Wall (ETC) |
✔ |
– |
– |
ETC specific properties |
Yes, Present_Value |
Errors On Device (ETC) |
✔ |
– |
– |
ETC specific properties |
N/A |
Timed Event (ETC) |
✔ |
✔ |
✔ |
ETC specific properties |
YES |
MACRO: Object ID (BACnet), Object Name, Object CID (Paradigm ID), Number and List of MetaData
PRESET: Object ID (BACnet), Object Name, Object CID (Paradigm ID), Number and List of MetaData
OVERRIDE: Object ID (BACnet), Object Name, Object CID (Paradigm ID), Number and List of MetaData
GROUP: Object ID (BACnet), Object Name, Object CID (Paradigm ID), Number and List of MetaData
SPACE: Object ID (BACnet), Object Name, Object CID (Paradigm ID), Space CID, Parent CID, Active Preset CID, Intensity, Number and List of Channels, Number and List of Presets, Number and List of Walls, Number and List of Child Spaces, Number and List of MetaData
ERRORs on DEVICE: Object ID (BACnet), Object Name, Device CID, Number and list of Errors
TIMED EVENT: Object ID (BACnet), Object Name, Object CID (Paradigm ID), Override CID, Space CID, Begin Time, End Time, Recurrence, Start Action, End Action, Number and List of Exceptions (limited to 3650), Number and List of MetaData
R BACnet IP, (Annex J)
£ BACnet IP, (Annex J), Foreign Device
£ ISO 8802-3, Ethernet (Clause 7)
£ ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
£ ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s) ____________
£ MS/TP master (Clause 9), baud rate(s):
£ MS/TP slave (Clause 9), baud rate(s):
£ Point-To-Point, EIA 232 (Clause 10), baud rate(s):
£ Point-To-Point, modem, (Clause 10), baud rate(s):
£ LonTalk, (Clause 11), medium: __________
£ BACnet/ZigBee (ANNEX O)
£ Other:
Indicating support for multiple character sets does not imply that they can all be supported.
£ ISO 10646 (UTF-8)
£ IBM™ / Microsoft™ DBCS
£ ISO 8859-1
R ANSI x3.4
£ ISO 10646 (UCS-2)
£ ISO 10646 (UCS-4)
£ JIS 0208
If this product is a communication gateway, describe the types of non-BACnet equipment / network(s) that the gateway supports:
Segmented Requests Supported | – Yes |
✔ No |
Window Size: |
Segmented Responses Supported | – Yes |
✔ No |
Window Size: |
£ Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
£ Annex H, BACnet Tunneling Router over IP
£ BACnet/IP Broadcast Management Device (BBMD)
DESCRIPTION AND LOCATION: 120 octets, including initial character set octet.
CREATED OBJECT NAMES: 64 octets maximum