BACnet PICS for P-CCS

This reference guide defines the BACnet Protocol Implementation Conformance Statement (PICS) for use with ETC's Unison Paradigm Central Control Server (P-CCS).

Unison Paradigm Central Control Server BACnet Interface

BACnet Protocol Implementation Conformance Statement (PICS)

Vendor Name: Electronic Theatre Controls, Inc. (ETC) – BACnet Vendor ID # 433

Product Name: Unison Paradigm Central Control Server

Product Model Number: P-CCS

Application Software Version: v5.0 or newer

1. Product Description

The P-CCS BACnet Interface allows a BACnet Client to interface with and control a Unison Paradigm lighting system. BACnet IP Clients physically connect via the Secondary Network Interface of the P-CCS, positioning the server as a gateway between the Unison system and BACnet client applications. It exposes a series of BACnet objects that reflect the state / condition of Paradigm lighting devices and permit control.

2. BACnet Conformance Class Supported

BACnet Standardized Device Profile (Annex L):

£ BACnet Operator Workstation (B-OWS)

£ BACnet Advanced Operator Workstation (B-AWS)

£ BACnet Operator Display (B-OD)

£ BACnet Building Controller (B-BC)

£ BACnet Advanced Application Controller (B-AAC)

£ BACnet Application Specific Controller (B-ASC)

£ BACnet Smart Sensor (B-SS)

£ BACnet Smart Actuator (B-SA)

R BACnet Gateway (B-GW)

List all BACnet Interoperability Building Blocks Supported (Annex K):

DS-RP-B

DS-RPM-B

DS-WP-B

DS-WPM-B

3. BACnet Standard Application Services Supported

Application Service Initiates Requests Executes Requests
Acknowledge Alarm
ConfirmedCOVNotification
ConfirmedEventNotification
GetAlarmSummary
GetEnrollmentSummary
SubscribeCOV

UnconfirmedCOVNotification

AtomicReadFile
AddListElement
RemoveListElement
CreateObject

DeleteObject

ReadProperty

ReadPropertyConditional
ReadPropertyMultiple

WriteProperty

WritePropertyMultiple

DeviceCommunicationControl
ConfirmedPrivateTransfer
ReinitializeDevice
ConfirmedTextMessage
UnconfirmedTextMessage
UTCTimeSynchronization

Who-Has
I-Have
Who-Is
I-Am

VT-Open
VT-Close
VT-Data
Authenticate
Request Key

4. Standard and Vendor-Proprietary Object Types Supported

Object-Type Supported Dynamically Creatable Dynamically Deletable Optional Properties Supported Writable
Properties

 

 

 

 

 

 

Analog Input

Description

 

Analog Output

Description

Present_Value
Analog Value

 

 

Binary Input

Description

 

Binary Output

Description

Present_Value
Binary Value

 

 

Calendar

See Timed Event below

See Timed Event below

Command

 

 

Device

N/A

N/A

 

Location,
Local_Time,
Local_Date

Event Enrollment

 

 

File

 

 

Group

 

 

Loop

 

 

Multi-state Input

 

 

Multi-state Output

 

 

Notification Class

 

 

Program

 

 

Schedule

(see Timed Event below)

(See Timed Event below)

Macro (ETC)

ETC specific properties

Yes, Present_Value

Preset (ETC)

ETC specific properties

Yes, Present_Value

Override (ETC)

ETC specific properties

Yes, Present_Value

Group (ETC)

ETC specific properties

Yes, Present_Value

Space (ETC)

ETC specific properties

Yes, Present_Value

Channel (ETC)

ETC specific properties

Yes, Present_Value

Wall (ETC)

ETC specific properties

Yes, Present_Value

Errors On Device (ETC)

ETC specific properties

N/A

Timed Event (ETC)

ETC specific properties

YES

Proprietary Object Type Properties

MACRO: Object ID (BACnet), Object Name, Object CID (Paradigm ID), Number and List of MetaData

PRESET: Object ID (BACnet), Object Name, Object CID (Paradigm ID), Number and List of MetaData

OVERRIDE: Object ID (BACnet), Object Name, Object CID (Paradigm ID), Number and List of MetaData

GROUP: Object ID (BACnet), Object Name, Object CID (Paradigm ID), Number and List of MetaData

SPACE: Object ID (BACnet), Object Name, Object CID (Paradigm ID), Space CID, Parent CID, Active Preset CID, Intensity, Number and List of Channels, Number and List of Presets, Number and List of Walls, Number and List of Child Spaces, Number and List of MetaData

ERRORs on DEVICE: Object ID (BACnet), Object Name, Device CID, Number and list of Errors

TIMED EVENT: Object ID (BACnet), Object Name, Object CID (Paradigm ID), Override CID, Space CID, Begin Time, End Time, Recurrence, Start Action, End Action, Number and List of Exceptions (limited to 3650), Number and List of MetaData

5. Data Link Layer Option

R BACnet IP, (Annex J)

£ BACnet IP, (Annex J), Foreign Device

£ ISO 8802-3, Ethernet (Clause 7)

£ ATA 878.1, 2.5 Mb. ARCNET (Clause 8)

£ ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s) ____________

£ MS/TP master (Clause 9), baud rate(s):

£ MS/TP slave (Clause 9), baud rate(s):

£ Point-To-Point, EIA 232 (Clause 10), baud rate(s):

£ Point-To-Point, modem, (Clause 10), baud rate(s):

£ LonTalk, (Clause 11), medium: __________

£ BACnet/ZigBee (ANNEX O)

£ Other:

6. Character Sets Supported

Indicating support for multiple character sets does not imply that they can all be supported.

£ ISO 10646 (UTF-8)

£ IBM™ / Microsoft™ DBCS

£ ISO 8859-1

R ANSI x3.4

£ ISO 10646 (UCS-2)

£ ISO 10646 (UCS-4)

£ JIS 0208

If this product is a communication gateway, describe the types of non-BACnet equipment / network(s) that the gateway supports:

7. Special Functionality

Segmented Requests Supported – Yes

✔ No

Window Size:
Segmented Responses Supported – Yes

✔ No

Window Size:

8. Router

£ Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.

£ Annex H, BACnet Tunneling Router over IP

£ BACnet/IP Broadcast Management Device (BBMD)

9. Property Range Restrictions:

DESCRIPTION AND LOCATION: 120 octets, including initial character set octet.

CREATED OBJECT NAMES: 64 octets maximum